IEEE Standards Interpretation for C57.12.00™-2000 Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers

Copyright © 2005 by the Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue New York, New York 10016-5997 USA All Rights Reserved.

Interpretations are issued to explain and clarify the intent of a standard and do not constitute an alteration to the original standard. In addition, interpretations are not intended to supply consulting information. Permission is hereby granted to download and print one copy of this document. Individuals seeking permission to reproduce and/or distribute this document in its entirety or portions of this document must contact the IEEE Standards Department for the appropriate license. Use of the information contained in this document is at your own risk.

IEEE Standards Department Copyrights and Permissions 445 Hoes Lane, Piscataway, New Jersey 08855-1331, USA

March 2005

Interpretation Request #1
Topic: Conflictive Situation Relevant Clauses: 4.1.6.1

The plant we have built up has two 2.500 KVA 13, 2-4, 16 kV transformers with +1- 2, 5- 5% taps under IEEE/ANSI. The voltage of the line is now between 13, .75-14.2 KV.

Our Customer understands that point 4.1.6.1 allows a +5% over voltage in any tap position for the transformers. They interpret IEEE Std C57.12.00 subclause 4.1.6.1 as if we could have a +5% margin in voltage in any tap, which means that if we have our transformers working in tap 1 = +5% , we could load the unit with a primary voltage up to 14.537 V. In fact they consider the 4.16 kv nominal voltage in the secondary, they increase this value in 5% making 4.368 kv ; they multiply this value by 3.328 that is the maximum transf. ratio value measured in the tap # 1 of the transformer and they come to the conclusion according to the specs the transformer shall be able to receive 14.537 kv in the primary.

On the contrary, we understand that subclause 4.1.6.1 defines an operation condition that will put the transformer into a maximum load and exitation = maximum heat. That extreme condition could be reach in any tap 0, -2,5% and -5% but never on taps +2, 5 and +5% since this operation conditions will imply that the primary voltage in the line will be over 13.860 volts, defined as limit voltage operation for a 13, 2 Kv system.

Could you please advise if we have the proper understanding of IEEE in this case?

Interpretation Response
IEEE Std C57.12.00-2000 (subclause 4.1.6.1) requires transformers to be suitable for operation, without exceeding temperature rise limits, under the following conditions:

  • at up to 110% of rated volts and up to 110% rated volts/hertz under no load condition, and;
  • with secondary winding at up to 105% of rated volts, and up to 105% rated volts/hertz, under full load condition

These requirements apply to all taps. Operation, under load, with primary voltage at 105% of rated tap voltage, for any tap position, is within the requirements of this standard.