This is an interpretation of ANSI C57.12.10-1997. Interpretations are issued to explain and clarify the intent of a standard and are not intended to constitute an alteration to the original standard or to supply consulting information. Permission is hereby granted to download and print one copy of this document. Individuals seeking permission to reproduce and/or distribute this document in its entirety or portions of this document must contact the IEEE Standard Department for the appropriate license. Use of the information contained in this document is at your own risk.
IEEE Standards Department
Copyrights and Permissions
445 Hoes Lane, P. O. Box 1331
Piscataway, New Jersey 08855-1331, USA
January 2005
Clause 5.5 Ground Pads.
Does part of this section refer to the ground pads on the lower exterior walls
of the transformer tank and another part refer
specifically to ground pads on the top of the tank? Or does 5.5.1 refer to pads
on the exterior walls of the tank, and 5.5.2 and 5.5.3 refer to pads on top
of the tank?
Clause 5.5 of the IEEE Std C57.12.10-1997 defines the specific construction,
location, and quantity of tank ground pads. Clause 5.5.1 describes how the pad
shall be constructed and attached to the tank. Clause 5.5.2 describes the quantity
and location of the pad for transformers 2500 kVA and smaller, while clause
5.5.3 does the same for the two pads required for transformers larger than 2500
kVA. These pads shall be located near the base, per clause 5.5.1. All other
ground pads are specified by the user. For example, ground pads for surge arresters
can be specified by the user per clause 9.12 or per the user's own requirements.