IEEE Standards Interpretations
for
IEEE Std C37.23-1987
Copyright © 2005 by the Institute of Electrical
and Electronics Engineers, Inc.
Three Park Avenue
New York, New York 10016-5997 USA
All Rights Reserved.
This is an interpretation of IEEE Std C37.23-1987. Interpretations are issued
to explain and clarify the intent of a standard and are not intended to constitute
an alteration to the original standard or to supply consulting information.
Permission is hereby granted to download and print one copy of this document.
Individuals seeking permission to reproduce and/or distribute this document
in its entirety or portions of this document must contact the IEEE Standard
Department for the appropriate license. Use of the information contained in
this document is at your own risk.
IEEE Standards Department
Copyrights and Permissions
445 Hoes
Lane
Piscataway, New Jersey 08855-1331, USA
March 2005
Interpretation #1
- Topic: Primary bus and connections
Relevant Clause: 2.1.1.1
-
-
- Why does IEEE Std C37.23-1987 use the words "primary bus and connections"?
-
- Why does IEEE Std. C37.23-1987 use the words "primary bus" instead
of "bus conductors" or "conductors of NSPBD"?
-
- Do these words mean just the portion of bars that income to the metal clad
switchgear or the entire length of a NSPBD system should be covered by insulated
material?
-
- What happens if a metal clad switchgear (as defined by ANSI C37.20.2) that
has the incoming part of the cubicle and Isolated Phase Bus Assembly (as defined
by ANSI C37.23) and the outgoing part of the cubicle connected to a NSPBA
without any insulation along bus conductor length? Is it correct?
-
- What happens if an insulation barrier at the bottom of the switchgear is
installed in order to make a physical separation between the Switchgear and
the NSPBA and continuing having the NSPBA without insulation, is it a valid
action?
-
- In case the switchgear was a Metal Enclosed Type, this problem would not
exist because this standard doesn't make any limitation of segregation on
that type of Switchgear.
Interpretation #1 IEEE Std C37.23-1987
The use of the term "primary bus and connections" in the second
paragraph of IEEE Std C37.23-1987, 2.1.1.1, item 1) is just a hold over from
the previous edition of the standard. It would be proper to interpret this
as phase conductors and their connections as opposed to ground conductor and
its connection.
Insulation requirements for metal-enclosed, non-segregated phase bus connecting
to metal-clad switchgear would apply to the entire run of bus -not just the
point of connection.
There are no requirements for insulation on metal-enclosed, isolated phase
bus in IEEE C37.23-1987.
Requirements for insulation on metal-enclosed, non-segregated phase bus
are not impacted by the connections to the other side of the metal-enclosed
switchgear.
Requirements for insulation on metal-enclosed, non-segregated phase bus are
not impacted by the installation of an "insulation barrier" installed
between the bus and the metal-enclosed switchgear.
-
-
-
Back to the list of Available IEEE Standards
Interpretations Online