IEEE Standards Interpretation for IEEE Std C57.13™-1993 IEEE Standard Requirements for Instrument Transformers
Copyright © 2002 by the Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue New York, New York 10016-5997 USA All Rights Reserved.
Interpretations are issued to explain and clarify the intent of a standard and do not constitute an alteration to the original standard. In addition, interpretations are not intended to supply consulting information. Permission is hereby granted to download and print one copy of this document. Individuals seeking permission to reproduce and/or distribute this document in its entirety or portions of this document must contact the IEEE Standards Department for the appropriate license. Use of the information contained in this document is at your own risk.
IEEE Standards Department Copyrights and Permissions 445 Hoes Lane, Piscataway, New Jersey 08855-1331, USA
January 2005
Interpretation Request #1
Topic: Calculating burdens at secondary currents other than 5-amps rated
Relevant Clause: Subclause 6.3, Table 9 - Table Notes; Subclause 6.4.1
For a CT with an 1 amp rated secondary current with an accuracy designation of O.3B2.0, what is the burden in ohms associated with this accuracy class?
Interpretation Response
The standard states that the VA is constant no matter what the secondary current
of the transformer. The B-2.0 burden is 2 ohms of impedance at 5 amperes secondary
current and per the standard is 50VA. Therefore, a transformer with a 1 ampere
secondary current would have a burden of 50 ohms impedance to maintain the 50VA.
Interpretation Request #2
Topic: Basic Impulse . . . design requirements
Relevant Clause: 3.4, 4.5, 4.7.2
Subclause 4.5 states the design requirements for Basic Impulse levels, dialectic tests.... It states exceptions for different type of transformers. The clause does not make exceptions for bushing type transformers. By default, bushing transformers would then be included in this design requirement.
Subclause 4.7.2 item a) does state this exception for routine tests of bushing type transformers.
Refer also to 3.4, "Bushing type transformers have no insulation for the primary winding."
Are basic impulse, dielectric test....design requirement according to 4.7.2 required for bushing type transformers?
Interpretation Response
Subclause 3.4 defines a bushing-type current transformer as an annular instrument
transformer without any insulation on the primary winding. Therefore, 4.7.2
is correct in omitting any test between the primary and secondary windings since
there is not any insulation between the primary and secondary windings on the
bushing-type current transformer.
Subclause 4.7.3 calls for impulse test for all instrument transformer primary insulation rated at nominal system voltages of 0.6kV or higher. Since bushing-type current transformers do not have any primary insulation, they do not meet this requirement and do not receive the impulse or primary applied tests.
If a annular current transformer does have a primary with a rated nominal system voltage, it would be a window-type current transformer as defined by 3.43.